| MODEL | TI100K | |
|
Power |
100KW |
|
|
Power Factor |
0.8 |
|
|
Input |
Phase |
3 phase 4 wire and ground |
|
Voltage Range |
380V± 20%(3 phase), phase voltage 220V |
|
|
Frequency Range |
45 – 65Hz |
|
|
Rectifier |
3 phase 6 pulses, 12 pulses is optional |
|
|
Outpu t |
Phase |
3 phase 4 wire and ground |
|
Wave form |
Pure sine wave |
|
|
Crest Factor |
3: 01 |
|
|
Rated voltage |
380/400/415V optional+ -1% for static load, 5% forfluctuant load |
|
|
Phase voltage setting |
200 - 244VAC, pls confirm when order |
|
|
Transient response |
+/-5%, 10ms |
|
|
Frequency |
50 / 60 Hz + / - 0.05% |
|
|
Total- harmonic dist ortion |
< 3% linear load, < 5%( nonlinear load) |
|
|
Short circuit current |
Short current for 0.1s (200% current) |
|
|
Overload capacity |
Overload 125% for 10 Mins, 125%-150% for 1min. automatically resume when load become normal |
|
|
Batter y |
Battery |
Maintenance free lead-acid cell |
|
DC Voltage |
384V |
|
|
Max Charge Current |
6-30A adjustable |
|
|
Bypas s |
Type |
Static state + manual maintenance bypass |
|
Input Phase |
3 phase 4 wire and ground |
|
|
Input voltage range |
15% - 25% (the front control panel selectable) |
|
|
Transfer time |
Inverter / bypass transfer switch time(Overload): 0ms inverter / bypass transfer switch time (fault inverter) 1ms |
|
|
Efficie ncy |
Whole unit |
> 85% |
|
Inverter |
95 |
|
|
Remote signaling |
Dry contact (battery low, battery discharging, bypass/ fault); output 12Vdc/80mA, Optional parts |
|
|
Communication interface |
RS232 ( SNMP, modem optional ) |
|
|
Running temperature |
0-40 degree Celsius |
|
|
Relative Humidity |
Less than 95% (without condensing) |
|
|
Noise at 1 M |
less than 60 dB |
|
| Degree of protection | IP20 | |
| Product size(mm) | 1200*900*1820 | |
| product weight(Kg) | 690 | |
| Package size(mm) | 1450*1110*1880 | |
| Package weight(Kg) | 750 | |